Amp Hour Calculator
Enter what you want to power and for how long. Get the amp hours to buy at your battery voltage, the energy in watt hours and how many 100 Ah or 200 Ah batteries that is.
To run 100 W for 10 hours through an inverter on a 12 V system you need about 93 Ah of LiFePO4 or 185 Ah of AGM, because lead-acid should only be drained halfway.
- Energy the load uses
- 1,000 Wh
- Bank to buy
- 1,111 Wh
- 100 Ah batteries
- 1
- 200 Ah batteries
- 1
Batteries are counted in parallel at the chosen voltage. Not sure of the watts? Look them up in the appliance wattage chart.
Amp hours to watt hours
Phone and laptop packs are rated at 3.6 to 3.7 V per lithium cell, not at the 5 V of the USB port; use 3.7 to match the label.
Wh = Ah × V · Ah = Wh ÷ V · Wh = mAh × V ÷ 1000
Amp hours needed at 12 V
LiFePO4 drained to 100%, through a 90% inverter. For AGM kept above half charge, double each figure.
| Load | 1 h | 4 h | 8 h | 24 h |
|---|---|---|---|---|
| 50 W | 5 Ah | 19 Ah | 37 Ah | 111 Ah |
| 100 W | 9 Ah | 37 Ah | 74 Ah | 222 Ah |
| 300 W | 28 Ah | 111 Ah | 222 Ah | 667 Ah |
| 500 W | 46 Ah | 185 Ah | 370 Ah | 1,111 Ah |
| 1000 W | 93 Ah | 370 Ah | 741 Ah | 2,222 Ah |
What battery amp hours mean
An amp hour is a charge of one amp flowing for one hour. The rating on a deep-cycle battery is measured over a set time, usually 20 hours for lead-acid (the C20 rate): a 100 Ah AGM battery is tested at 5 A until it reaches about 10.5 V. Draw faster than that and a lead-acid battery delivers fewer amp hours, an effect described by Peukert's law. Lithium iron phosphate cells lose very little capacity at higher currents.
Amp hours on their own do not compare batteries of different voltages. A 24 V 100 Ah battery holds twice the energy of a 12 V 100 Ah battery. Compare in watt hours, and size cables and fuses from amps.
How to calculate the amp hours you need
- Find the energy. Multiply the load in watts by the hours it runs: 100 W for 10 hours is 1,000 Wh.
- Allow for the inverter. If the load runs on AC through an inverter, divide by its efficiency, usually 0.85 to 0.95. DC loads skip this step.
- Allow for usable depth. Divide by the share of the battery you will actually use: about 1.0 for LiFePO4, 0.5 for lead-acid or AGM if you want it to last.
- Convert to amp hours. Divide by the battery voltage (12, 24 or 48 V). Round up to whole batteries.
Ah = W × hours ÷ (V × depth × inverter efficiency)
Planning for cloudy days on solar? Multiply by the number of days you want the bank to carry the load without charging. To check a backup plan against a generator instead, use the generator size calculator.
Questions
What does Ah stand for on a battery?
Amp hours. A 100 Ah battery can, in theory, deliver 1 amp for 100 hours or 5 amps for 20 hours. Amp hours only describe energy once you also know the voltage: watt hours = amp hours × volts.
How many watt hours is a 12V 100Ah battery?
1,200 Wh. At 24 V the same 100 Ah would hold 2,400 Wh, which is why bigger systems move to 24 or 48 V.
How long will a 12V 100Ah battery last?
Running 100 W through a 90% efficient inverter, a LiFePO4 battery lasts about 10.8 hours; a lead-acid battery kept above 50% lasts about 4.8. Try your own load in the battery runtime calculator.
How much is 40,000 mAh in Wh?
At the 3.7 V of a lithium-ion cell, 40,000 mAh is 148 Wh. Power banks above 100 Wh need airline approval to fly.
Is 100Wh the same as 10,000mAh?
Not quite. 10,000 mAh at 3.7 V is 37 Wh. 100 Wh at 3.7 V is about 27,027 mAh.
Why only use half of a lead-acid battery?
Lead-acid and AGM batteries wear out much faster when drained deeply. Stopping at 50% roughly doubles or triples their cycle life compared with draining them flat. LiFePO4 cells tolerate near-full discharge, and their battery management system already reserves a margin.
Depth-of-discharge defaults follow common practice for LiFePO4 and lead-acid deep-cycle batteries; your battery's datasheet takes priority. Formulas and test cases on how we calculate. Last checked November 2026.